给水排水毕业设计内容

武汉科技大学城市学院

毕业设计

设计题目: 研究

学部:

专业:10级

学号:[1**********]0

姓名: 指导老师:...

摘要………………………………………………………… ABSTRC……………………………………………………… 第一卷 第一册 设计说明…………………………………

第二卷 第二册 工程概算书………………………………

第三卷 第三册 图纸目录…………………………………

参考文献……………………………………………………

致谢…………………………………………………………

附录1 外文参考文献(译文)……………………………

附录2 外文参考文献(原文)……………………………

宜居新城一期建筑给排水工程设计

研究

摘 要

本设计的建筑为一十三层的商住楼,给排水工程设计包括了室内生活给水系统设计,室内排水系统设计,室内消防给水系统设计,以及雨水系统设计。生活给水系统分为两个区:地下室至三层为低区,采用市政给水管网直接供水;四层至二十三层为高区,利用屋顶高位水箱给系统供水。消防给水系统分为消火栓给水系统和自动喷淋灭火系统,本建筑为一类民用建筑,而其建筑高度≥50m,按《高层民用建筑防火设计规范》规定,室内消火栓用水量和室外消火栓用水量分别取20L/s和15L/s,自动喷淋系统计算用水量为16L/s,自动喷淋系统在屋顶设增压设备。排水系统采用污废合流制,排水系统采用特殊的伸顶通气单立管排水系统,通气冒高出屋顶1.00m。给水系统采用PP-R给水管材,消火栓给水系统和自动喷淋灭火系统采用无缝镀锌钢管,排水系统立管采用PPI螺旋排水管,各层排水支管采用普通的UPVC排水管。在地下层设贮水池和加压泵房,地下室另设集水坑,集水坑中设潜污泵,保证污水及时排出。

关键词:建筑 给水 消防 排水

Abstract

Work in the complex building for23 floors of trade in the building originally designed, is it drain off water engineering design including room is it supply water system design , indoor fire control supply water the system is designed and the indoor drainage system set up to live to give. Life supplies water and is divided into two districts systematically: The ground lower floor to 3floor are the low district, adopt the pipe network of municipal water supply and supply water directly; 4are the high district to the 23th Floor, supply water for the system with the high-order water tank of the roof. Fire control supply water system divide into fire hydrant supply water system and automatic spray fire extinguishing system, building this one building, but area its does not exceed 1000m2, stipulate according to " high-story civil building fire prevention the design specification ", water consumption of the indoor fire hydrant and outdoor fire hydrant water consumption fetch 20L/s and15L/s respectively, automatic spray systematic water consumption fetch 16L/s, automatic spray system set up the pressurized equipment on the roof. Supply water system adopt PP-R supply water pipe , fire hydrant supply water system and automatic spray fire extinguishing system adopted and has not sewn the zinc-plated steel tube , the drainage system sets up and is in charge of adopting PPI spiral drain pipe, drain off water and prop up in charge of adopting ordinary UPVC drain piping on the everyth floor. Sets up the storage cistern and pressurizes in the pump house in the ground lower floor, the basement sets up and collects the puddle separately , collect and set up and sneak the corrupt pump in the puddle, guarantee sewages are discharged in time.

Key word : Building Supply water Fire control Spray

宜居新城一期建筑给排水工程设计

研究

第一卷 第一册 设计说明书

武汉科技大学城市学院

二零一四年五月

目 录

第一卷 第一册 设计说明

1.工程概述

1.1设计任务

1.2 设计参考依据及设计资料

1.3 设计成果

2.设计说明

2.1 室内给水系统

2.1.1水源及给水工艺的选择

2.1.2给水系统组成

2.1.3设计参数及生活用水量

2.1.4管道布置及设备安装要求

2.2 室内消火栓给水系统

2.2.1系统的选择

2.2.2系统的组成

2.2.3消防管道及设备安装要求

2.3 室内排水系统

2.3.1 排水系统的选择

2.3.2 排水系统的组成

2.3.3 排水管道的安装要求

1工程概况

1.1设计任务

按照上级批准的设计任务书规定,完成某13层(地下一层)商住楼建筑给排水工程设计。

要求设计室内给排水工程与土建工程配套,具体项目为:

1、建筑给水工程

2、建筑排水工程

3、建筑消防给水工程

1.2 设计参考依据及设计资料

1、《建筑给排水设计规范》(GB50015-2003)

2、《建筑设计防火规范》(GBJ16-87)

3、《高层民用建筑设计防火规范》(GB50045-95)

4、《自动喷水灭火系统设计规范》(GB50084-2001)

5、《水喷雾灭火系统设计规范》(GB50219-95)

6、建筑提供的各层平面图等条件图

7、基本资料

拟建一栋13层的商住楼,建筑高度46.4米。地下一层,地上13层,一、二层为商业用,均设有公共卫生间。3至13层为公寓,每户均按3.0人计。

该建筑物北侧道路下有市政给水管道,管径为DN400,常年可提供的资用水头为0.30MP,允许接管径为DN200,大楼40米范围无室外消火栓,污水管管径为DN600,管顶埋深为2.4米,雨水管管径为DN1200,管顶埋深为1.6米。

8、气象资料

该市气候温和,地质条件较好。最大积雪深度为200mm。

1.3 设计成果

1、毕业设计说明书、计算书

毕业设计说明书、计算书主要包括以下内容:工程概况(包括设计依据、设计资料、

设计规模等),给水方案的选择,各系统的设计计算(包括建筑内部给水系统、排水系统、消火栓给水系统的设计计算,有增压、贮水设备的要进行增压、贮水设备的计算及选型等),其它内容(包括目录、中英文摘要、参考文献、小结等)。

2、设计图纸

毕业设计图纸包括各层给水系统、排水系统、消火栓系统平面布置图,给水系统、排水系统、消火栓系统各系统图,卫生间大样图。要求图面布局合理,正确清晰,用工程字注文,符合制图标准及有关规定。

2设计说明

该建筑共13层,地下一层及一层为4.75米,二层为3.9米,三层至十三层为2.8米,建筑高度为46.4米。

2.1 室内给水系统

2.1.1水源及给水工艺的选择

由《给排水设计手册》可知:内部给水系统应尽量利用外部给水管网的水压直接供水。在外部管网水压不能满足整个建筑或建筑小区的用水要求时,则建筑物的下层或地势较低的建筑,应尽量利用外管网的水压直接供水,上层或地势较高的建筑设置加压和流量调节装置供水。

由设计资料可知:市政管网可供水压为0.3MP,此水压远不能满足用水要求,故需二次加压,所以必须分区供水。考虑到本建筑地下一层主要为停车区,一二层为商用区,三层及以上为公寓,故选择地下一层及一二层为低区,三层及以上为高区。同时,由于该楼体中部存在楼面平接及墙体交接变形缝,故横向分区供水,分为左区和右区。

生活区的给水可以用到二种方式:①由增压水泵直接加压供给的下行上给式;②由高水箱供给的上行下给式。

方案一:低区-1-2层利用市政管网水压供水,高区3-13层利用变频泵从生活水池吸水供水。

方案二:低区-1-2层利用市政管网水压供水,高区3-13层利用高位水箱供水,在中间设置减压阀进行减压。

方案一的优点是供水可以随时间变化,水泵的流量由变频控制,自动改变水泵的转

速,使水泵经常处于高效状态,能量损耗小。缺点是需要一套较贵的变速水泵及其自动控制设备,且维修较复杂。方案二的优点是减压阀不占楼层的房间的面积,使建筑物的面积发挥最大的经济效益,其缺点是减压阀宜损坏,有较大的能量损耗。

经方案比较,该建筑有足够的空间设置减压阀,本设计应该采用第二方案。

2.1.2给水系统组成

本建筑的给水系统是:

低区为-1至2层,采用下行上给供水方式,即城市管网直接供低区各卫生器具。 高区为3至13层,共11层,采用上行下给供水方式, 用高位水箱供水,中间设置减压阀。

即城市管网→地下贮水池→水泵→屋顶水箱→高区各卫生器具。

低区由引入管、水表节点、给水管网和附件组成,高区由引入管、水表节点、地下贮水池、水泵、屋顶水箱、给水管网及附件组成。

2.1.3设计参数及生活用水量

2.1.4管道布置及设备安装要求

(1)给水管道采用给水钢管,供水箱管也采用钢管。

(2)各层给水管采用暗装敷设,支管以2%的坡度坡向池水装置。

(3)给水管与排水管平行、交叉时,其距离分别大于0.5m 和0.15m,交叉处给水管道在上。

(4)管道穿越墙壁时,需预留孔洞,孔洞尺寸采用:d+50mm--d+100mm,管道穿过楼板时应预埋金属套管。

(5)在立管和横管上设闸阀,当d50mm,设闸阀。

(6)水泵基础应高于地面0.1m,水泵采用自动启动。

2.2室内消火栓给水系统

2.2.1系统的选择

根据《给排水设计手册-建筑给排水》第二版,该建筑为二类高层建筑。本设计的对象是13层的小高层,高度不超过50米, 根据规范建筑高度不超过50米的高层建筑,一旦发生火灾消防车从室外消火栓或消防水池,通过水泵接合器向室内管道送水仍然可以加强室内的管网供水能力,协助救火。故本设计选用消火栓给水系统。

室内消火栓给水系统有为分区、不分区两种方式。消火栓的静水压力超过0.80MPa时就需要分区供水,而本设计是13层的小高层,高度不超过50米,静水压力小于0.80MPa, 可以不分区。由于本设计的建筑是13层小高层商住楼,火灾的隐患少,人员疏散也快,扑救难度不大。无须设置长年的高压消防给水,因此消火栓给水系统采用临时高压给水系统。

此建筑为二类高层建筑,不分区,建筑高度小于50m,根据《规范》要求:室内消防流量取20L/S,每根竖管最小流量10L/S,每支水枪最小流量5L/S。管网竖向及水平成环网,且保证相邻两支消火栓水枪充实水柱同时到达室内任何部位,系统消火栓充实水柱不小于10米,栓处静水压力不大于80米,当动压超过50米时,设置减压孔板进行加压。

消火栓布置在明显、经常有人出入、而且使用方便的地方,其间距不大于30m。一层至十三层每层均设置7根立管。消防水池设在地下一层,室外消火栓采用地上式,沿建筑布置。屋顶水箱贮有10min的消防水量24m3。室外消火栓系统设有四个水泵结合器,以便消防车向室内管网供水。

2.2.2系统的组成

消火栓系统由消防水池,消防水泵,消防管网,减压阀,消火栓和水泵结合器组成。

2.2.3消防管道及设备安装要求

1)管材采用热浸镀锌钢管,连接采用光沟槽式机械接头。

2)消火栓立管采用DN100mm,消火栓口径为65mm,水枪喷嘴口径为19mm,水龙带为麻质,

直径65mm,长度25m。

3) 使各层消火栓出水流量接近设计值,在高区的下层消火栓前装设减压阀进行减压,

2.3 室内排水系统 2.3.1 排水系统的选择

根据《给排水设计手册-建筑给排水》第二版,排水系统划分为合流制和分流制两种。分流制:指粪便污水与生活废水,生产污水与生产废水在建筑物内部分开用管道排至室外。合流制:指粪便污水与生活废水,生产污水与生产废水在建筑物内部混合用同一根管道排到室外。结合本设计的具体情况拟定本设计的排水系统排水方式为合流制。 本建筑为商住楼,要求排水安全可靠,故本设计中的排水管道采用专用通气立管,采用双立管排水系统。对于地下一层的雨水及污水,先进入集水坑,再由潜污泵提升出去,一二层单独排水,三至十三层单独排水。

2.3.2 排水系统的组成

该系统由卫生器具,排水管道,检查口,清扫口,伸缩节,室外排水管道,检查井,潜污泵,集水井等组成。

2.3.3排水管道的安装要求

(1)污水立管采用双壁中空内螺旋消音塑料排水管,密封胶圈接口,各层排水支管采用普通UPVC排水管,粘接方式连接。排除横管采用A型柔性接口铸铁管。 (2)排水立管在垂直方向转弯处,采用两个450弯头连接。 (3)排水立管穿越楼板应预留孔洞,安装时应设金属防水套管,

(4)立管沿墙敷设时,其轴线与墙面距离(L)不得小于下述规定:DN=50mm,,L=100mm;;DN=75mm,,L=150mm;;DN=100mm,,L=150mm;;DN=150mm,,L=200mm. (5)排水检查井中心线与建筑物外墙距不小与2m.

(6)排水检查井为0.7m*0.7m*1.5m

(7)排水立管上设检查口,隔层设一个,离地面1m。此外,各排水横支管起始端有位置的需设清扫口,以便清通。上面住宅可不设清扫口,需设地漏.。

(8)考虑到温度变化因素,而且层高为2.8m〈4m,排水立管上每层设一个伸缩节。

宜居新城一期建筑给排水工程设计

研究

第二卷 第二册 设计计算书

武汉科技大学城市学院 二零一四年五月

目 录

第一卷 第一册 设计说明

1.室内给水系统计算 1.1给水量计算 1.2管网水力计算

1.3 构筑物及其他设计计算 2.室内消火栓系统计算 2.1消火栓系统用水量 2.2消火栓系统水力计算 2.3消防水池和水箱 3.室内排水系统计算 3.1排水系统设置 3.2排水管网计算 3.3地下层集水坑排水

1设计计算

3.1

室内给水系统计算

3.1.1给水量计算

由《给排水设计手册-建筑给排水》第二版可确定各单位用水量参数,详见下表3.1。

表3.1 给水量计算表

未预见用水量取10%,则总用水量为16.52×(1+10%)=18.17m3/h。 3.1.2管网水力计算

根据《给排水设计手册-建筑给排水》第二版可知 生活给水设计秒流量计算公式采用: q=0.2α√Ng

对于商铺,α取1.5,对于服务型公寓,α取2.2。

图 3.1 低区给水立管1

由图3.1及表3.2可知,此区的最不利给水点管段应为0~6、6~9、9~18、18~27、

27~31、31~市政给水末端 这条主干管上,因此由表可计算得此给水立管1上最不利点的水头损失之和为 21.406 mH2O,即相当于0.214MPa。

低区由市政直接供水,而市政给水管网常年可提供的水压为 0.3MPa,大于0.214MPa,满足要求。

图3.2 低区给水立管2

表3.3 1-JL2水力计算表

由图3.2及表3.3可知,此区的最不利给水点管段应为0~4、4~7、7~10、10~19、

19~25、25~市政给水末端 这条主干管上,因此由表可计算得此给水立管1上最不利点的水头损失之和为 19.488 mH2O,即相当于0.195MPa。

低区由市政直接供水,而市政给水管网常年可提供的水压为 0.3MPa,大于0.195MPa,满足要求。

图3.3 高区给水立管1

表 3.4 2-JL1水力计算表图

图3.4 高区给水立管2

3.1.3构筑物及其他设计计算

(1)生活水池容积计算

由表3.1可知 Qh = 16.52 m3/h ,因分区而设有二个生活水池,故每个水池容积V= 8.26m3 ,由此可选定水池进水管采用DN80铸铁管,流速v=0.5~0.6m/s,查给水排水设计手册,其进水流量为 Q=10.08m/s。

每个生活水池的有效高度 H=1.5m, L * B * H=3m * 2m * 1.5m (2)高位水箱容积计算

同样由于分区,高位水箱也分为二个,而高位水箱只为了给高区供水,其 Qh = 13.03 m3/h,故每个水箱容积为6.52m3 选用smc水箱 L×B×H=2.5m×2.5m×1.5m 高位水箱安装高度计算公式: Zx≥Zb+0.1Hx+100H3 式中 Zx :水箱最低水位的标高(m); Zb : 最不利配水点的标高(m);

Hx : 由水箱出口至最不利配水点的管道全部水头损失(KPa); H3 : 最不利配水点所需的最低工作压力(MPa); 经计算得高区给水立管1上水箱的安装高度为: Zx≥37.850+0.1*26.417+100*0.05=45.49m 取安装高度为45.50m。 高区2立管水箱安装高度:

Zx≥37.850+0.1*24.389+100*0.05=45.289m 取安装高度为45.30m。

(3)水箱水位计算

水箱的出水管高于水箱底200mm,所以高区1立管上水箱最低水位为45.70m,2立管上水箱最低水位为45.50m,水箱有250mm的保护高,则高区1立管上水箱最高水位为47.45m,2立管上水箱最高水位为47.25m。 (4)水泵的选择及减压阀的设置

水池最低水位至水箱最高水位的高度为:

HST=47.45-(-4.75)=52.20( m )

水泵的压力管长估算为:

L=52.20+26.417=78.617m

考虑到水泵处的局部水头损失,扬程取80m,查《建筑给排水计手册》选得水泵为: 型号IS50-32-250型单级离心卧式泵,一用一备共两台,流量 3.47 m3/h,扬程80m,电机功率11KW.

该建筑给水立管中水压过大,因而需设减压阀,既设置比例式减压阀,减压阀分别设在三层至八层给水支管处,阀后压力为0.35MPa。 (5)水表的选择

(1)连接与2-JL-1立管上的每层进户水表

设计秒流量qg0.73L/s=2.628m3/h, ,选旋翼式LXS-21水表,公称直径25mm,最大流量15m3/h,公称流量为8m3/h。

Qmax82

0.64 此处取用公称流量 Kb

100100

2.6282

Hb10.79Kp

Kb0.64(2)连接与2-JL-2立管上的每层进户水表

由于高区左右两给水区基本对称,因此,所用进户水表也与1区的一样,3/h,公称流量为8m3/h。

qg

2

3.2 室内消火栓给水系统计算

本建筑为一类民用高层建筑,因本建筑高度不足80米所以不必分区。

图 3.5 消防系统图

3.2.1消火栓系统用水量

本建筑属于二类高建筑的商住楼。本建筑地下部分深4.75米,地上部分高46.4米,根据《高层民用建筑设计防火规范》规定,室内消火栓用水量为20L/S,每根竖管最小流量为10L/S,每支水枪最小流量5L/S。

查《建筑给排水设计手册上》P511,表6.2-15,选用DN65的消火栓,喷口直径d=19mm,水龙带长度Ld=25m,充实水柱长度Hm=12m,喷口系数B=1.577,ф=0.0097,实验系数αf=1.21,麻织水龙带Az=0.0043 。火灾延续时间为2h。室内消火栓的布置原则为同一平面2支水枪的2股充实水柱同时到达任何部位。消火栓离地面1.1米。

3.2.2消火栓系统水力计算

由给水排水设计手册-建筑给排水可知: 消火栓保护半径:Ld=25×0.8=20m

Ls=Hmcos450=6.30m R=Ld+Ls=26.30m

消火栓采用单排布置间距为 S≤R2b2=26.30214.502=21.94m

该建筑总长92.0m,宽36.5m,高46.4m ,一至二楼为商铺,三楼及以上为公寓,结合建筑结构布局27.5m的间距过大,实际安装距离变小也能满足要求,详见布置图。 根据防火规范,此建筑发生火灾时室内需2支水枪同时工作,每根消防竖管上需1支水枪同时工作,简图中消防XHL-01号竖管上的13层消火栓离消防水泵最高最远,处于系统最不利位置。

XHL-01号消防竖管13层消火栓的水枪造成10 m充实水柱时所 需的压力值为

Hq

10fHm1fHm

10*1.21*12

169.00 (KPa)

10.0097*1.21*12

水枪喷射流量:

qxhBHq.1577*169.005.16L/s >5L/s 故能够满足要求。

消火栓口所需水压 Hxh=Hq+hd+Hk

而 Hq=16.90mH2O,Hk=2mH2O

2

hd=A2Ldq2=0.00430×25×5.16=2.86mH2O xh

Hxh=16.90+2.86+2=21.76mH2O

最不利点消火栓静水压力 H=40.95-37.75=3.2mH2O

按《高层民用建筑设计放火规范》规定设增压设施,设置增压泵和空气罐。

按最不利点消防竖管和消火栓的流量分配要求最不利消防竖管出水枪数为2支,次不利管出水枪数2支,相邻消火栓竖管出水枪数为2支。

Hxh0=hd+Hq+Hk=21.76mH2O

初步确定竖管直径为DN100,当消防流量达到10L/s时,管内流速为:

4101034Q

V===1.27m/s

3.140.13.14D

节点12处消火栓口的压力为:

Hxh1=Hxh0+H+h=21.76+2.8+0.297=24.86mH2O

2qxh2

由于 Hxh1=Hq1+hd=1ALdqxh1

B

所以水枪射流流量为: qxh1=

Hxh1Hk22.462224.86

==5.55L/s 

1.004325ALd0

0.0043251..577B1577

1点的水枪射流量:

Hxh2=Hxh1+H+h=24.86+2.8+2.215=29.88mH2O 由 qxh2

Hxh2= q2xh2/B+ Az×Ld×qxh22 +2 得: qxh229.882=6.05L/s

10.0043251.577

则可知管路总水头损失为Hw=49.416*1.1=54.358kPa

消火栓给水系统所需的总水压为 Hx=40.950+21.760+54.358=117.07mH2O 水泵流量 QX=35.52L/S

选择消火栓泵为XBD系列专用消防水泵两台,型号选取XBD(HW)9/10/,一备一用。其设计参数:流量Q=41.12L/S,扬程Hp=150m,n=2980r/min,电机功率N=132kw。

3.2.3消防水池和水箱

(1)室内消防用水量为20L/s水箱存储10min的消防用水量,其贮水量为

Vx

20*10*60

=12m3

1000

选用smc水箱L×B×H=3m×2m×2m

根据消防用水量20L/S,设2组水泵结合器。火灾初期10min消防用水量由屋顶水箱供应,10min后则由消火栓处启动泵按钮直接启动地下室消防水泵供应。

当消火栓栓口出水压力超过0.5MPa时,使用减压装置。 (2)高层建筑火灾延续时间为2小时,

所以消防水池 V=20×2×3.6=144m3 设置时分为两个 其中消防水池进水管DN150mm 流速为1.5m/s。 每个水池有效高度H=2.5m 取 L×B×H=6m×5m×2.7m

3.3 室内排水系统计算

本建筑采用污废合流制,并设有单独的通气管,即采用双立管方式。

3.3.1排水系统设置

由于本建筑地下一层为停车库,1~2层为商铺,每个商铺都有各自的卫生间,3~13层为住宅,有单独卫生间。故地下一层的污水排入地下一层的集水井,经排污泵提升

后排至室外检查井,一二层单排,3层以上排水立管引致一层后经水井排至室外。

3.3.2排水管网计算

生活排水设计秒流量计算公式采用:

q0.12NPqmax

对于商铺,α取2.5,对于公寓,α取1.5 塑料排水管采用标准坡度为 i=0.026 (1)WL-S1上的排水管段的水力计算

图3.6 WL-S1计算简图 表

(2)WL-S2上的排水管段的水力计算

图3.7 WL-S2计算简图 表

(3)WL-Z1上的排水管段的水力计算

如下图3.8所示WL-Z1立管上的有7支立管,且每根支立管上的公寓户型相同,各立管上的户型相同,所以7支立管只需计算一支立管即可,在此计算WL-1。

图3.8 WL-Z1计算简图

图3.9 WL-1立管计算简图

在图3.8 中横干管计算表如下:

(4)WL-Z2上的排水管段的水力计算

图3.10 WL-Z2计算简图

如上图3.10所示,分析平面图知,该平面图上公寓布置左右对称,户型单一,

故排水WL-Z2与WL-Z1对称,其水力计算同上二表,不在作此重复计算,故复制修改如下:

图3.11 WL-14计算简图

在图3.10 中横干管计算表如下:

3.3.3地下层集水坑排水

地下一层车库设置若干个集水坑,收集消防系统泄水和路面冲洗的泄水,大小为L*B*H=1.5m * 1.5m * 1.2m ,每个集水坑选用二台WQ-40-10-22,Q=40m3/h,H=10m,配套电机功率为3kw。

宜居新城一期建筑给排水工程设计

研究

第三卷 第三册 图纸目录

武汉科技大学城市学院 二零一四年五月

参考文献

1. 《建筑给排水设计规范》(GB50015-2003) 2. 《建筑设计防火规范》(GBJ16-87) 3. 《高层民用建筑设计防火规范》(GB50045-95) 4. 《自动喷水灭火系统设计规范》(GB50084-2001) 5. 《水喷雾灭火系统设计规范》(GB50219-95) 6. 《给水排水设计手册》(第二版) 7. 《建筑给水排水工程(第六版)》(中国建筑工业出版社) 8. 建筑提供的各层平面图等条件图

致 谢

在这次设计过程中,我加深了对书本的理解,进一步熟悉了规范,对本专业知识也有了更深的认识。其中也发现了自己一些不足之处,有待在以后的学习和工作中进一步提高。在设计过程中,我学到了很多东西,这些都使我受益匪浅。从设计刚开始老师们就对我严格要求,悉心指导,使我学会了很多事情的处理方式,我不仅学到了很多专业方面的知识,也学到了很多事情的处理方式和做人的道理。

请允许我对老师们近一段时间来对我的毕业设计给予的耐心的指导真诚的表示感谢!有老师们对我无私的指导是我的荣幸,老师们的教导给了我莫大的鼓舞,感谢老师! 在我完成设计的过程中,老师总是定时检查我的进程情况,及时的指出我设计中出现的问题,并耐心的给我讲解如何去解决这些问题。老师对学生是那么的负责任,而且是那样的平易近人,有了老师的指导我的毕业设计才得以按时按质的完成。

老师对自己的工作是那样的一丝不苟,对学生的学业是那样的关心和负责,这让我在深受感动的同时也有了几分的自责。因为这毕竟花费了老师休息的时间,毕竟消耗了老师的精力,我对老师关怀学生的学习的热情表达最真诚的敬意!对老师在我毕业设计完成过程中给予的无私指导和帮助表达最真诚的谢意!

已经无法用语言来表达我心中想说的话,我就用行动来证明吧!我会在毕业设计答辩中最好的表现自己,在以后的学习和工作中加倍努力,做出成绩,我想这才是对老师最好的报答

附录1 外文参考文献(译文)

你快回去哦,回家能找到……

译文标题

武汉科技大学城市学院

毕业设计

设计题目: 研究

学部:

专业:10级

学号:[1**********]0

姓名: 指导老师:...

摘要………………………………………………………… ABSTRC……………………………………………………… 第一卷 第一册 设计说明…………………………………

第二卷 第二册 工程概算书………………………………

第三卷 第三册 图纸目录…………………………………

参考文献……………………………………………………

致谢…………………………………………………………

附录1 外文参考文献(译文)……………………………

附录2 外文参考文献(原文)……………………………

宜居新城一期建筑给排水工程设计

研究

摘 要

本设计的建筑为一十三层的商住楼,给排水工程设计包括了室内生活给水系统设计,室内排水系统设计,室内消防给水系统设计,以及雨水系统设计。生活给水系统分为两个区:地下室至三层为低区,采用市政给水管网直接供水;四层至二十三层为高区,利用屋顶高位水箱给系统供水。消防给水系统分为消火栓给水系统和自动喷淋灭火系统,本建筑为一类民用建筑,而其建筑高度≥50m,按《高层民用建筑防火设计规范》规定,室内消火栓用水量和室外消火栓用水量分别取20L/s和15L/s,自动喷淋系统计算用水量为16L/s,自动喷淋系统在屋顶设增压设备。排水系统采用污废合流制,排水系统采用特殊的伸顶通气单立管排水系统,通气冒高出屋顶1.00m。给水系统采用PP-R给水管材,消火栓给水系统和自动喷淋灭火系统采用无缝镀锌钢管,排水系统立管采用PPI螺旋排水管,各层排水支管采用普通的UPVC排水管。在地下层设贮水池和加压泵房,地下室另设集水坑,集水坑中设潜污泵,保证污水及时排出。

关键词:建筑 给水 消防 排水

Abstract

Work in the complex building for23 floors of trade in the building originally designed, is it drain off water engineering design including room is it supply water system design , indoor fire control supply water the system is designed and the indoor drainage system set up to live to give. Life supplies water and is divided into two districts systematically: The ground lower floor to 3floor are the low district, adopt the pipe network of municipal water supply and supply water directly; 4are the high district to the 23th Floor, supply water for the system with the high-order water tank of the roof. Fire control supply water system divide into fire hydrant supply water system and automatic spray fire extinguishing system, building this one building, but area its does not exceed 1000m2, stipulate according to " high-story civil building fire prevention the design specification ", water consumption of the indoor fire hydrant and outdoor fire hydrant water consumption fetch 20L/s and15L/s respectively, automatic spray systematic water consumption fetch 16L/s, automatic spray system set up the pressurized equipment on the roof. Supply water system adopt PP-R supply water pipe , fire hydrant supply water system and automatic spray fire extinguishing system adopted and has not sewn the zinc-plated steel tube , the drainage system sets up and is in charge of adopting PPI spiral drain pipe, drain off water and prop up in charge of adopting ordinary UPVC drain piping on the everyth floor. Sets up the storage cistern and pressurizes in the pump house in the ground lower floor, the basement sets up and collects the puddle separately , collect and set up and sneak the corrupt pump in the puddle, guarantee sewages are discharged in time.

Key word : Building Supply water Fire control Spray

宜居新城一期建筑给排水工程设计

研究

第一卷 第一册 设计说明书

武汉科技大学城市学院

二零一四年五月

目 录

第一卷 第一册 设计说明

1.工程概述

1.1设计任务

1.2 设计参考依据及设计资料

1.3 设计成果

2.设计说明

2.1 室内给水系统

2.1.1水源及给水工艺的选择

2.1.2给水系统组成

2.1.3设计参数及生活用水量

2.1.4管道布置及设备安装要求

2.2 室内消火栓给水系统

2.2.1系统的选择

2.2.2系统的组成

2.2.3消防管道及设备安装要求

2.3 室内排水系统

2.3.1 排水系统的选择

2.3.2 排水系统的组成

2.3.3 排水管道的安装要求

1工程概况

1.1设计任务

按照上级批准的设计任务书规定,完成某13层(地下一层)商住楼建筑给排水工程设计。

要求设计室内给排水工程与土建工程配套,具体项目为:

1、建筑给水工程

2、建筑排水工程

3、建筑消防给水工程

1.2 设计参考依据及设计资料

1、《建筑给排水设计规范》(GB50015-2003)

2、《建筑设计防火规范》(GBJ16-87)

3、《高层民用建筑设计防火规范》(GB50045-95)

4、《自动喷水灭火系统设计规范》(GB50084-2001)

5、《水喷雾灭火系统设计规范》(GB50219-95)

6、建筑提供的各层平面图等条件图

7、基本资料

拟建一栋13层的商住楼,建筑高度46.4米。地下一层,地上13层,一、二层为商业用,均设有公共卫生间。3至13层为公寓,每户均按3.0人计。

该建筑物北侧道路下有市政给水管道,管径为DN400,常年可提供的资用水头为0.30MP,允许接管径为DN200,大楼40米范围无室外消火栓,污水管管径为DN600,管顶埋深为2.4米,雨水管管径为DN1200,管顶埋深为1.6米。

8、气象资料

该市气候温和,地质条件较好。最大积雪深度为200mm。

1.3 设计成果

1、毕业设计说明书、计算书

毕业设计说明书、计算书主要包括以下内容:工程概况(包括设计依据、设计资料、

设计规模等),给水方案的选择,各系统的设计计算(包括建筑内部给水系统、排水系统、消火栓给水系统的设计计算,有增压、贮水设备的要进行增压、贮水设备的计算及选型等),其它内容(包括目录、中英文摘要、参考文献、小结等)。

2、设计图纸

毕业设计图纸包括各层给水系统、排水系统、消火栓系统平面布置图,给水系统、排水系统、消火栓系统各系统图,卫生间大样图。要求图面布局合理,正确清晰,用工程字注文,符合制图标准及有关规定。

2设计说明

该建筑共13层,地下一层及一层为4.75米,二层为3.9米,三层至十三层为2.8米,建筑高度为46.4米。

2.1 室内给水系统

2.1.1水源及给水工艺的选择

由《给排水设计手册》可知:内部给水系统应尽量利用外部给水管网的水压直接供水。在外部管网水压不能满足整个建筑或建筑小区的用水要求时,则建筑物的下层或地势较低的建筑,应尽量利用外管网的水压直接供水,上层或地势较高的建筑设置加压和流量调节装置供水。

由设计资料可知:市政管网可供水压为0.3MP,此水压远不能满足用水要求,故需二次加压,所以必须分区供水。考虑到本建筑地下一层主要为停车区,一二层为商用区,三层及以上为公寓,故选择地下一层及一二层为低区,三层及以上为高区。同时,由于该楼体中部存在楼面平接及墙体交接变形缝,故横向分区供水,分为左区和右区。

生活区的给水可以用到二种方式:①由增压水泵直接加压供给的下行上给式;②由高水箱供给的上行下给式。

方案一:低区-1-2层利用市政管网水压供水,高区3-13层利用变频泵从生活水池吸水供水。

方案二:低区-1-2层利用市政管网水压供水,高区3-13层利用高位水箱供水,在中间设置减压阀进行减压。

方案一的优点是供水可以随时间变化,水泵的流量由变频控制,自动改变水泵的转

速,使水泵经常处于高效状态,能量损耗小。缺点是需要一套较贵的变速水泵及其自动控制设备,且维修较复杂。方案二的优点是减压阀不占楼层的房间的面积,使建筑物的面积发挥最大的经济效益,其缺点是减压阀宜损坏,有较大的能量损耗。

经方案比较,该建筑有足够的空间设置减压阀,本设计应该采用第二方案。

2.1.2给水系统组成

本建筑的给水系统是:

低区为-1至2层,采用下行上给供水方式,即城市管网直接供低区各卫生器具。 高区为3至13层,共11层,采用上行下给供水方式, 用高位水箱供水,中间设置减压阀。

即城市管网→地下贮水池→水泵→屋顶水箱→高区各卫生器具。

低区由引入管、水表节点、给水管网和附件组成,高区由引入管、水表节点、地下贮水池、水泵、屋顶水箱、给水管网及附件组成。

2.1.3设计参数及生活用水量

2.1.4管道布置及设备安装要求

(1)给水管道采用给水钢管,供水箱管也采用钢管。

(2)各层给水管采用暗装敷设,支管以2%的坡度坡向池水装置。

(3)给水管与排水管平行、交叉时,其距离分别大于0.5m 和0.15m,交叉处给水管道在上。

(4)管道穿越墙壁时,需预留孔洞,孔洞尺寸采用:d+50mm--d+100mm,管道穿过楼板时应预埋金属套管。

(5)在立管和横管上设闸阀,当d50mm,设闸阀。

(6)水泵基础应高于地面0.1m,水泵采用自动启动。

2.2室内消火栓给水系统

2.2.1系统的选择

根据《给排水设计手册-建筑给排水》第二版,该建筑为二类高层建筑。本设计的对象是13层的小高层,高度不超过50米, 根据规范建筑高度不超过50米的高层建筑,一旦发生火灾消防车从室外消火栓或消防水池,通过水泵接合器向室内管道送水仍然可以加强室内的管网供水能力,协助救火。故本设计选用消火栓给水系统。

室内消火栓给水系统有为分区、不分区两种方式。消火栓的静水压力超过0.80MPa时就需要分区供水,而本设计是13层的小高层,高度不超过50米,静水压力小于0.80MPa, 可以不分区。由于本设计的建筑是13层小高层商住楼,火灾的隐患少,人员疏散也快,扑救难度不大。无须设置长年的高压消防给水,因此消火栓给水系统采用临时高压给水系统。

此建筑为二类高层建筑,不分区,建筑高度小于50m,根据《规范》要求:室内消防流量取20L/S,每根竖管最小流量10L/S,每支水枪最小流量5L/S。管网竖向及水平成环网,且保证相邻两支消火栓水枪充实水柱同时到达室内任何部位,系统消火栓充实水柱不小于10米,栓处静水压力不大于80米,当动压超过50米时,设置减压孔板进行加压。

消火栓布置在明显、经常有人出入、而且使用方便的地方,其间距不大于30m。一层至十三层每层均设置7根立管。消防水池设在地下一层,室外消火栓采用地上式,沿建筑布置。屋顶水箱贮有10min的消防水量24m3。室外消火栓系统设有四个水泵结合器,以便消防车向室内管网供水。

2.2.2系统的组成

消火栓系统由消防水池,消防水泵,消防管网,减压阀,消火栓和水泵结合器组成。

2.2.3消防管道及设备安装要求

1)管材采用热浸镀锌钢管,连接采用光沟槽式机械接头。

2)消火栓立管采用DN100mm,消火栓口径为65mm,水枪喷嘴口径为19mm,水龙带为麻质,

直径65mm,长度25m。

3) 使各层消火栓出水流量接近设计值,在高区的下层消火栓前装设减压阀进行减压,

2.3 室内排水系统 2.3.1 排水系统的选择

根据《给排水设计手册-建筑给排水》第二版,排水系统划分为合流制和分流制两种。分流制:指粪便污水与生活废水,生产污水与生产废水在建筑物内部分开用管道排至室外。合流制:指粪便污水与生活废水,生产污水与生产废水在建筑物内部混合用同一根管道排到室外。结合本设计的具体情况拟定本设计的排水系统排水方式为合流制。 本建筑为商住楼,要求排水安全可靠,故本设计中的排水管道采用专用通气立管,采用双立管排水系统。对于地下一层的雨水及污水,先进入集水坑,再由潜污泵提升出去,一二层单独排水,三至十三层单独排水。

2.3.2 排水系统的组成

该系统由卫生器具,排水管道,检查口,清扫口,伸缩节,室外排水管道,检查井,潜污泵,集水井等组成。

2.3.3排水管道的安装要求

(1)污水立管采用双壁中空内螺旋消音塑料排水管,密封胶圈接口,各层排水支管采用普通UPVC排水管,粘接方式连接。排除横管采用A型柔性接口铸铁管。 (2)排水立管在垂直方向转弯处,采用两个450弯头连接。 (3)排水立管穿越楼板应预留孔洞,安装时应设金属防水套管,

(4)立管沿墙敷设时,其轴线与墙面距离(L)不得小于下述规定:DN=50mm,,L=100mm;;DN=75mm,,L=150mm;;DN=100mm,,L=150mm;;DN=150mm,,L=200mm. (5)排水检查井中心线与建筑物外墙距不小与2m.

(6)排水检查井为0.7m*0.7m*1.5m

(7)排水立管上设检查口,隔层设一个,离地面1m。此外,各排水横支管起始端有位置的需设清扫口,以便清通。上面住宅可不设清扫口,需设地漏.。

(8)考虑到温度变化因素,而且层高为2.8m〈4m,排水立管上每层设一个伸缩节。

宜居新城一期建筑给排水工程设计

研究

第二卷 第二册 设计计算书

武汉科技大学城市学院 二零一四年五月

目 录

第一卷 第一册 设计说明

1.室内给水系统计算 1.1给水量计算 1.2管网水力计算

1.3 构筑物及其他设计计算 2.室内消火栓系统计算 2.1消火栓系统用水量 2.2消火栓系统水力计算 2.3消防水池和水箱 3.室内排水系统计算 3.1排水系统设置 3.2排水管网计算 3.3地下层集水坑排水

1设计计算

3.1

室内给水系统计算

3.1.1给水量计算

由《给排水设计手册-建筑给排水》第二版可确定各单位用水量参数,详见下表3.1。

表3.1 给水量计算表

未预见用水量取10%,则总用水量为16.52×(1+10%)=18.17m3/h。 3.1.2管网水力计算

根据《给排水设计手册-建筑给排水》第二版可知 生活给水设计秒流量计算公式采用: q=0.2α√Ng

对于商铺,α取1.5,对于服务型公寓,α取2.2。

图 3.1 低区给水立管1

由图3.1及表3.2可知,此区的最不利给水点管段应为0~6、6~9、9~18、18~27、

27~31、31~市政给水末端 这条主干管上,因此由表可计算得此给水立管1上最不利点的水头损失之和为 21.406 mH2O,即相当于0.214MPa。

低区由市政直接供水,而市政给水管网常年可提供的水压为 0.3MPa,大于0.214MPa,满足要求。

图3.2 低区给水立管2

表3.3 1-JL2水力计算表

由图3.2及表3.3可知,此区的最不利给水点管段应为0~4、4~7、7~10、10~19、

19~25、25~市政给水末端 这条主干管上,因此由表可计算得此给水立管1上最不利点的水头损失之和为 19.488 mH2O,即相当于0.195MPa。

低区由市政直接供水,而市政给水管网常年可提供的水压为 0.3MPa,大于0.195MPa,满足要求。

图3.3 高区给水立管1

表 3.4 2-JL1水力计算表图

图3.4 高区给水立管2

3.1.3构筑物及其他设计计算

(1)生活水池容积计算

由表3.1可知 Qh = 16.52 m3/h ,因分区而设有二个生活水池,故每个水池容积V= 8.26m3 ,由此可选定水池进水管采用DN80铸铁管,流速v=0.5~0.6m/s,查给水排水设计手册,其进水流量为 Q=10.08m/s。

每个生活水池的有效高度 H=1.5m, L * B * H=3m * 2m * 1.5m (2)高位水箱容积计算

同样由于分区,高位水箱也分为二个,而高位水箱只为了给高区供水,其 Qh = 13.03 m3/h,故每个水箱容积为6.52m3 选用smc水箱 L×B×H=2.5m×2.5m×1.5m 高位水箱安装高度计算公式: Zx≥Zb+0.1Hx+100H3 式中 Zx :水箱最低水位的标高(m); Zb : 最不利配水点的标高(m);

Hx : 由水箱出口至最不利配水点的管道全部水头损失(KPa); H3 : 最不利配水点所需的最低工作压力(MPa); 经计算得高区给水立管1上水箱的安装高度为: Zx≥37.850+0.1*26.417+100*0.05=45.49m 取安装高度为45.50m。 高区2立管水箱安装高度:

Zx≥37.850+0.1*24.389+100*0.05=45.289m 取安装高度为45.30m。

(3)水箱水位计算

水箱的出水管高于水箱底200mm,所以高区1立管上水箱最低水位为45.70m,2立管上水箱最低水位为45.50m,水箱有250mm的保护高,则高区1立管上水箱最高水位为47.45m,2立管上水箱最高水位为47.25m。 (4)水泵的选择及减压阀的设置

水池最低水位至水箱最高水位的高度为:

HST=47.45-(-4.75)=52.20( m )

水泵的压力管长估算为:

L=52.20+26.417=78.617m

考虑到水泵处的局部水头损失,扬程取80m,查《建筑给排水计手册》选得水泵为: 型号IS50-32-250型单级离心卧式泵,一用一备共两台,流量 3.47 m3/h,扬程80m,电机功率11KW.

该建筑给水立管中水压过大,因而需设减压阀,既设置比例式减压阀,减压阀分别设在三层至八层给水支管处,阀后压力为0.35MPa。 (5)水表的选择

(1)连接与2-JL-1立管上的每层进户水表

设计秒流量qg0.73L/s=2.628m3/h, ,选旋翼式LXS-21水表,公称直径25mm,最大流量15m3/h,公称流量为8m3/h。

Qmax82

0.64 此处取用公称流量 Kb

100100

2.6282

Hb10.79Kp

Kb0.64(2)连接与2-JL-2立管上的每层进户水表

由于高区左右两给水区基本对称,因此,所用进户水表也与1区的一样,3/h,公称流量为8m3/h。

qg

2

3.2 室内消火栓给水系统计算

本建筑为一类民用高层建筑,因本建筑高度不足80米所以不必分区。

图 3.5 消防系统图

3.2.1消火栓系统用水量

本建筑属于二类高建筑的商住楼。本建筑地下部分深4.75米,地上部分高46.4米,根据《高层民用建筑设计防火规范》规定,室内消火栓用水量为20L/S,每根竖管最小流量为10L/S,每支水枪最小流量5L/S。

查《建筑给排水设计手册上》P511,表6.2-15,选用DN65的消火栓,喷口直径d=19mm,水龙带长度Ld=25m,充实水柱长度Hm=12m,喷口系数B=1.577,ф=0.0097,实验系数αf=1.21,麻织水龙带Az=0.0043 。火灾延续时间为2h。室内消火栓的布置原则为同一平面2支水枪的2股充实水柱同时到达任何部位。消火栓离地面1.1米。

3.2.2消火栓系统水力计算

由给水排水设计手册-建筑给排水可知: 消火栓保护半径:Ld=25×0.8=20m

Ls=Hmcos450=6.30m R=Ld+Ls=26.30m

消火栓采用单排布置间距为 S≤R2b2=26.30214.502=21.94m

该建筑总长92.0m,宽36.5m,高46.4m ,一至二楼为商铺,三楼及以上为公寓,结合建筑结构布局27.5m的间距过大,实际安装距离变小也能满足要求,详见布置图。 根据防火规范,此建筑发生火灾时室内需2支水枪同时工作,每根消防竖管上需1支水枪同时工作,简图中消防XHL-01号竖管上的13层消火栓离消防水泵最高最远,处于系统最不利位置。

XHL-01号消防竖管13层消火栓的水枪造成10 m充实水柱时所 需的压力值为

Hq

10fHm1fHm

10*1.21*12

169.00 (KPa)

10.0097*1.21*12

水枪喷射流量:

qxhBHq.1577*169.005.16L/s >5L/s 故能够满足要求。

消火栓口所需水压 Hxh=Hq+hd+Hk

而 Hq=16.90mH2O,Hk=2mH2O

2

hd=A2Ldq2=0.00430×25×5.16=2.86mH2O xh

Hxh=16.90+2.86+2=21.76mH2O

最不利点消火栓静水压力 H=40.95-37.75=3.2mH2O

按《高层民用建筑设计放火规范》规定设增压设施,设置增压泵和空气罐。

按最不利点消防竖管和消火栓的流量分配要求最不利消防竖管出水枪数为2支,次不利管出水枪数2支,相邻消火栓竖管出水枪数为2支。

Hxh0=hd+Hq+Hk=21.76mH2O

初步确定竖管直径为DN100,当消防流量达到10L/s时,管内流速为:

4101034Q

V===1.27m/s

3.140.13.14D

节点12处消火栓口的压力为:

Hxh1=Hxh0+H+h=21.76+2.8+0.297=24.86mH2O

2qxh2

由于 Hxh1=Hq1+hd=1ALdqxh1

B

所以水枪射流流量为: qxh1=

Hxh1Hk22.462224.86

==5.55L/s 

1.004325ALd0

0.0043251..577B1577

1点的水枪射流量:

Hxh2=Hxh1+H+h=24.86+2.8+2.215=29.88mH2O 由 qxh2

Hxh2= q2xh2/B+ Az×Ld×qxh22 +2 得: qxh229.882=6.05L/s

10.0043251.577

则可知管路总水头损失为Hw=49.416*1.1=54.358kPa

消火栓给水系统所需的总水压为 Hx=40.950+21.760+54.358=117.07mH2O 水泵流量 QX=35.52L/S

选择消火栓泵为XBD系列专用消防水泵两台,型号选取XBD(HW)9/10/,一备一用。其设计参数:流量Q=41.12L/S,扬程Hp=150m,n=2980r/min,电机功率N=132kw。

3.2.3消防水池和水箱

(1)室内消防用水量为20L/s水箱存储10min的消防用水量,其贮水量为

Vx

20*10*60

=12m3

1000

选用smc水箱L×B×H=3m×2m×2m

根据消防用水量20L/S,设2组水泵结合器。火灾初期10min消防用水量由屋顶水箱供应,10min后则由消火栓处启动泵按钮直接启动地下室消防水泵供应。

当消火栓栓口出水压力超过0.5MPa时,使用减压装置。 (2)高层建筑火灾延续时间为2小时,

所以消防水池 V=20×2×3.6=144m3 设置时分为两个 其中消防水池进水管DN150mm 流速为1.5m/s。 每个水池有效高度H=2.5m 取 L×B×H=6m×5m×2.7m

3.3 室内排水系统计算

本建筑采用污废合流制,并设有单独的通气管,即采用双立管方式。

3.3.1排水系统设置

由于本建筑地下一层为停车库,1~2层为商铺,每个商铺都有各自的卫生间,3~13层为住宅,有单独卫生间。故地下一层的污水排入地下一层的集水井,经排污泵提升

后排至室外检查井,一二层单排,3层以上排水立管引致一层后经水井排至室外。

3.3.2排水管网计算

生活排水设计秒流量计算公式采用:

q0.12NPqmax

对于商铺,α取2.5,对于公寓,α取1.5 塑料排水管采用标准坡度为 i=0.026 (1)WL-S1上的排水管段的水力计算

图3.6 WL-S1计算简图 表

(2)WL-S2上的排水管段的水力计算

图3.7 WL-S2计算简图 表

(3)WL-Z1上的排水管段的水力计算

如下图3.8所示WL-Z1立管上的有7支立管,且每根支立管上的公寓户型相同,各立管上的户型相同,所以7支立管只需计算一支立管即可,在此计算WL-1。

图3.8 WL-Z1计算简图

图3.9 WL-1立管计算简图

在图3.8 中横干管计算表如下:

(4)WL-Z2上的排水管段的水力计算

图3.10 WL-Z2计算简图

如上图3.10所示,分析平面图知,该平面图上公寓布置左右对称,户型单一,

故排水WL-Z2与WL-Z1对称,其水力计算同上二表,不在作此重复计算,故复制修改如下:

图3.11 WL-14计算简图

在图3.10 中横干管计算表如下:

3.3.3地下层集水坑排水

地下一层车库设置若干个集水坑,收集消防系统泄水和路面冲洗的泄水,大小为L*B*H=1.5m * 1.5m * 1.2m ,每个集水坑选用二台WQ-40-10-22,Q=40m3/h,H=10m,配套电机功率为3kw。

宜居新城一期建筑给排水工程设计

研究

第三卷 第三册 图纸目录

武汉科技大学城市学院 二零一四年五月

参考文献

1. 《建筑给排水设计规范》(GB50015-2003) 2. 《建筑设计防火规范》(GBJ16-87) 3. 《高层民用建筑设计防火规范》(GB50045-95) 4. 《自动喷水灭火系统设计规范》(GB50084-2001) 5. 《水喷雾灭火系统设计规范》(GB50219-95) 6. 《给水排水设计手册》(第二版) 7. 《建筑给水排水工程(第六版)》(中国建筑工业出版社) 8. 建筑提供的各层平面图等条件图

致 谢

在这次设计过程中,我加深了对书本的理解,进一步熟悉了规范,对本专业知识也有了更深的认识。其中也发现了自己一些不足之处,有待在以后的学习和工作中进一步提高。在设计过程中,我学到了很多东西,这些都使我受益匪浅。从设计刚开始老师们就对我严格要求,悉心指导,使我学会了很多事情的处理方式,我不仅学到了很多专业方面的知识,也学到了很多事情的处理方式和做人的道理。

请允许我对老师们近一段时间来对我的毕业设计给予的耐心的指导真诚的表示感谢!有老师们对我无私的指导是我的荣幸,老师们的教导给了我莫大的鼓舞,感谢老师! 在我完成设计的过程中,老师总是定时检查我的进程情况,及时的指出我设计中出现的问题,并耐心的给我讲解如何去解决这些问题。老师对学生是那么的负责任,而且是那样的平易近人,有了老师的指导我的毕业设计才得以按时按质的完成。

老师对自己的工作是那样的一丝不苟,对学生的学业是那样的关心和负责,这让我在深受感动的同时也有了几分的自责。因为这毕竟花费了老师休息的时间,毕竟消耗了老师的精力,我对老师关怀学生的学习的热情表达最真诚的敬意!对老师在我毕业设计完成过程中给予的无私指导和帮助表达最真诚的谢意!

已经无法用语言来表达我心中想说的话,我就用行动来证明吧!我会在毕业设计答辩中最好的表现自己,在以后的学习和工作中加倍努力,做出成绩,我想这才是对老师最好的报答

附录1 外文参考文献(译文)

你快回去哦,回家能找到……

译文标题


相关文章

  • 给排水工程专业初中级职称考试大纲2015(定)
  • 给排水工程专业初中级专业技术职务任职资格考试大纲 (2015年修订) 第一章 考试说明 一.考试目的 给排水工程专业初中级专业技术资格考试是以专业技术为基础,考核和评定工程技术人员能力和水平的一种考试,目的是为了建立起更加公正.合理的专业技 ...查看


  • 高层综合楼设计范例图纸给排水专业识图全面讲解
  • [转] 高层综合楼设计范例图纸给排水专业识图全面讲解 (一) 内容提要 本章围绕本教材给出的某高层综合楼范例,介绍建筑设备中给排水专业识图的有关内容,包括:给排水专业工图图纸内容.常用给水.排水.消火栓.自动喷淋系统的主要组成部分以及各系统 ...查看


  • 海绵城市建设国家建筑标准设计体系
  • 海绵城市建设国家建筑标准设计体系 2016年1月 前言 新时期大力推进建设自然积存.自然渗透.自然净化的"海绵城市",是党中央.国务院确定的一项重大战略,对于推进新型城镇发展,保护和改善城市生态环境,促进生态文明建设具有 ...查看


  • 自来水厂实习报告要求
  • 自来水厂实习报告要求 一. 实习的目的.性质及要求 通过近三年的理论学习和一系列的课程设计实践环节的训练,学生在基础理论.应用技术和专业知识等诸方面已初步具备了给水排水专业的业务知识.但是,将所学的理论知识应用于科学研究和工程设计尚有一个过 ...查看


  • 4给排水--简答
  • 一. 简答题(共10道题,每题10分,总分100分) 1.我公司的安全"十字"方针是什么? 2.我公司的"作业指导书"共有几套,都是什么? 3.根据公司Q/JLECSC•01-WP16-2002文件中 ...查看


  • 建筑给排水课程设计
  • 目录 第一章 课程设计任务书 一. 原始数据..................................................1 二. 参考文献....................................... ...查看


  • 建筑给排水毕业设计任务书(酉阳电力大厦)
  • 毕 业 设 计 任 务 书 一.题目:酉阳力电大厦 二.目的要求 1.毕业设计是本科学员在校学完教学计划规定的全部课程后所必须进行的重要实践性环节.通过工程设计,综合利用和深化所学专业理论知识,培养独立工作能力及分析解决一般工程实际问题的能 ...查看


  • 建筑工程设计文件编制深度规定(给排水初步设计部分)
  • 给排水初步设计文件编制深度规定 1.1 在初步设计阶段,建筑工程给水排水专业设计文件应包括设计说明书.设计图纸.主要设备器材表.计算书(计算书是内部作业文件,当主管部门组织设计文件审查要求提供计算书时,应按要求提供相关的计算书,计算书不属于 ...查看


  • 排水防涝讲课
  • 快速城镇化背景下的排水防涝综合规划 --城市排水(雨水)防涝综合规划编制大纲解读 谢映霞 中国城市规划设计研究院 2014年6月20日 主要内容 1.排水(雨水)防涝综合规划大纲背景 形势与挑战 城市排水内涝成因分析 2. 排水(雨水)防涝 ...查看


  • 给水专业设计图纸编制统一要求和规定
  • 给水专业设计图纸编制统一要求和规定 总则 1.1 编制依据 (1) 我院编制的<质量体系文件>(2000年): (2) 建设部城市建设司修编的<市政工程设计技术管理标准>(1993年): (3) 建设部修编的< ...查看


热门内容