单相接地故障的特征及处理
【摘要】10kV(35kV)小电流接地系统单相接地(以下简称单相接地)是配电系统最常见的故障,多发生在潮湿、多雨天气。由于树障、配电线路上绝缘子单相击穿、单相断线以及小动物危害等诸多因素引起的。单相接地不仅影响了用户的正常供电,而且可能产生过电压,烧坏设备,甚至引起相间短路而扩大事故。因此,熟悉接地故障的处理方法对值班人员来说十分重要。
【关键词】:单相接地故障; 过电压; 处理
【 abstract 】 : 10 kV (35 kV) the small current grounding system single-phase grounding (hereinafter referred to as the single-phase grounding) is the most common fault distribution system, occurs in damp, wet weather. Because ShuZhang distribution circuit, the insulator single-phase breakdown, and small animals harm single-phase break many reasons. Single-phase grounding not only affects the normal supply of users, and can produce overvoltage, burn out equipment, and even cause alternate with short circuit and expand the accident. Therefore, familiar with ground fault treatment is very important to the officer on duty.
【 keywords 】 : phase-to-ground fault; Overvoltage; processing
1、几种接地故障的特征
(1)当发生一相(如A相)不完全接地时,即通过高电阻或电弧接地,这时故障相的电压降低,非故障相的电压升高,它们大于相电压,但达不到线电压。电压互感器开口三角处的电压达到整定值,电压继电器动作,发出接地信号。
(2)如果发生A相完全接地,则故障相的电压降到零,非故障相的电压升高到线电压。此时电压互感器开口三角处出现100V电压,电压继电器动作,发出接地信号。
(3)电压互感器高压侧出现一相(A相)断线或熔断件熔断,此时故障相的指示不为零,这是由于此相电压表在二次回路中经互感器线圈和其他两相电压表形成串联回路,出现比较小的电压指示,但不是该相实际电压,非故障相仍为相电压。互感器开口三角处会出现35V左右电压值,并启动继电器,发出接地信号。
(4)由于系统中存在容性和感性参数的元件,特别是带有铁芯的铁磁电感元件,在参数组合不匹配时会引起铁磁谐振,并且继电器动作,发出接地信号。
(5)空载母线虚假接地现象。在母线空载运行时,也可能会出现三相电压不平衡,并且发出接地信号。但当送上一条线路后接地现象会自行消失。
2、单相接地故障的处理
单相接地故障的特征及处理
【摘要】10kV(35kV)小电流接地系统单相接地(以下简称单相接地)是配电系统最常见的故障,多发生在潮湿、多雨天气。由于树障、配电线路上绝缘子单相击穿、单相断线以及小动物危害等诸多因素引起的。单相接地不仅影响了用户的正常供电,而且可能产生过电压,烧坏设备,甚至引起相间短路而扩大事故。因此,熟悉接地故障的处理方法对值班人员来说十分重要。
【关键词】:单相接地故障; 过电压; 处理
【 abstract 】 : 10 kV (35 kV) the small current grounding system single-phase grounding (hereinafter referred to as the single-phase grounding) is the most common fault distribution system, occurs in damp, wet weather. Because ShuZhang distribution circuit, the insulator single-phase breakdown, and small animals harm single-phase break many reasons. Single-phase grounding not only affects the normal supply of users, and can produce overvoltage, burn out equipment, and even cause alternate with short circuit and expand the accident. Therefore, familiar with ground fault treatment is very important to the officer on duty.
【 keywords 】 : phase-to-ground fault; Overvoltage; processing
1、几种接地故障的特征
(1)当发生一相(如A相)不完全接地时,即通过高电阻或电弧接地,这时故障相的电压降低,非故障相的电压升高,它们大于相电压,但达不到线电压。电压互感器开口三角处的电压达到整定值,电压继电器动作,发出接地信号。
(2)如果发生A相完全接地,则故障相的电压降到零,非故障相的电压升高到线电压。此时电压互感器开口三角处出现100V电压,电压继电器动作,发出接地信号。
(3)电压互感器高压侧出现一相(A相)断线或熔断件熔断,此时故障相的指示不为零,这是由于此相电压表在二次回路中经互感器线圈和其他两相电压表形成串联回路,出现比较小的电压指示,但不是该相实际电压,非故障相仍为相电压。互感器开口三角处会出现35V左右电压值,并启动继电器,发出接地信号。
(4)由于系统中存在容性和感性参数的元件,特别是带有铁芯的铁磁电感元件,在参数组合不匹配时会引起铁磁谐振,并且继电器动作,发出接地信号。
(5)空载母线虚假接地现象。在母线空载运行时,也可能会出现三相电压不平衡,并且发出接地信号。但当送上一条线路后接地现象会自行消失。
2、单相接地故障的处理